LIFECORD – FRHF (i) 300V

Conductor
Stranded copper conductor
Insulation
XLPE + Mica tape
Stranding
Pairs and copper drain wire cabled together
Screen
Aluminium polyester tape
Sheath
LSZH Thermoplastic
Standard colour orange
Reference standard
EN 50288-7
Application
Fire-resistant individually and collectively screened cable for instrumentation and communication applications.
For fixed installation where the cable has to maintain its functionality during fire.
Core identification
Pair colours white/blue
Black identification numbers
Min. Bending Radius (Installation/fixed)
9xØ∕6xØ
Rated voltage
300 V
Fire performance
IEC 60332-1-2
IEC 60332-3-22
Fire-resistant
Ø < 20 mm IEC 60331-2
Ø > 20 mm IEC 60331-1
Halogen-free
IEC 60754 series
Smoke emission
IEC 61034 series
Min. installation temperature
-15 ° C
Operating temperature
-40 °C – 90 °C
Loop (pair, max 20 °C) (ohm/km)
52
Pair capacitance (nom. 1 kHz) (nF/km)
55
Loop inductance (nom.) (mH/km)
0.6
Insulation resistance (20 °C) (Mohm/km)
≥ 1500